Simplex 4007ES or 4100ES: sizing an addressable fire alarm panel

Points, notification circuits, power and networking, from the Simplex datasheets
November 26, 2026 by
Simplex 4007ES or 4100ES: sizing an addressable fire alarm panel

The first question for an addressable panel is how many devices it must carry today and later. Every smoke sensor, heat sensor, manual station and module takes an address on the panel's signaling line circuit (SLC).

4007ES – up to 250 points – 4007-9101

The 4007ES Hybrid has one IDNet 2 SLC for up to 100 addressable points, and up to 250 with two 4007-9803 loop expansion modules. It has four onboard Class A/B notification circuits (NACs), a 6 A power supply and battery charger, an 8-point zone/relay module for conventional zones or relays, and a 4.3-inch color touchscreen. The cabinet holds batteries up to 18 Ah; 25 Ah and 33 Ah batteries need the 4009-9801 external battery cabinet. It can work alone or on an ES Net or 4120 network.

4100ES – up to 3,000 points – 4100-9701

The 4100ES Master Controller includes the CPU, an IDNet 2 card for up to 250 points, the ES power supply with a battery charger for up to 110 Ah, and an RUI+ port for remote annunciators. The CPU handles up to 3,000 addressable points, and the panel grows with optional modules: 4100-5450 conventional NAC module, 4100-5451 IDNAC addressable notification module, relay and network modules. Boxes and doors are ordered separately.

Networking

Both panels can join a Simplex network (ES Net or 4120). On a 4010ES, the 4010-9922 network interface card connects the panel to a 4120 network of up to 99 nodes per loop, using wired or fiber media cards.

In short

  • Up to 100 devices, or up to 250 with loop expansion: the 4007ES.
  • Larger buildings, more devices, more circuits or many modules: the 4100ES.
  • Several buildings or panels that must work together: a networked system.

Send us your device count and drawings for a quotation. Every product page has the datasheet and UL listing to download.