Product details
| Part number | 4100-9701 |
|---|---|
| Description | Master Controller with 2x40 Display |
| Category | Fire Alarm Control Panels / 4100ES Panels & Bays |
| System | Simplex 4100ES fire alarm panels |
| Works with | IDNet 2 devices and TrueAlarm sensors, ES Net network, 4120 network, MAPNET II devices (optional module), … |
| Approvals | UL, ULC; 4100ES series: UL 864 Fire Detection and Control (UOJZ), CAN/ULC-S527, FM approved, NYC MEA35-93E |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-9701
Master Controller for the 4100ES addressable fire alarm panel, supplied with an English 2x40 character LCD operator interface. It includes the CPU card, an IDNet 2 card for up to 250 addressable/analog points, the ES power supply with a 110 Ah battery charger, and an external RUI+ port for remote annunciators. The CPU handles up to 3000 addressable points, and the panel is expanded with optional NAC, IDNAC, relay and network modules.
Boxes and door/retainer assemblies are ordered separately (data sheet S4100-0037), and the listed currents do not include IDNet, NAC or IDNAC loads.
Specifications
| Display | 2x40 Display - English |
|---|---|
| IDNet 2 card | supports up to 250 addressable/analog points |
| Panel capacity | up to 3000 addressable points |
| AC input | 120 V to 240 V 50/60 Hz |
| Current (without IDNet devices) | Supv. 277 mA; Alarm 321 mA |
| Total DC output (ES-PS) | 9.5 A without fan; 12.7 A with 4100-5131 fan, without a 4100-5451 IDNAC module |
| Battery charging | up to 110 Ah (batteries larger than 50 Ah require a remote battery cabinet) |
| Operating temperature / humidity | 32°F to 120°F (0°C to 49°C); up to 93% RH, non-condensing at 90°F (32°C) maximum |
Used with
- 4100-5450 – Conventional NAC module, three 3 A NACs (1 block)
- 4100-5451 – IDNAC addressable notification SLC module, three 3 A SLCs (2 blocks, ES power supply only)
- 4100-2300 – Expansion bay assembly, one for each expansion bay
- 4100-0647 – 240 VAC PDM harness; one PDM harness per power supply (120/220/230 VAC versions: 4100-0644/0645/0646)
- 4100-6033 – Alarm relay module, three Form C relays, 2 A at 32 VDC
From Simplex datasheet S4100-1031. The datasheet and UL listing can be downloaded under Documents above.