Product details
| Part number | 2099-9767 |
|---|---|
| Description | Pull Station Intrin Safe, in/O |
| Category | Manual Call Points & Release Stations / Manual Call Points / Pull Stations |
| System | Simplex fire alarm systems |
| Works with | Simplex intrinsically safe barrier modules 2081-9062 / 2081-9063 |
| Approvals | FM approved as intrinsically safe (with Simplex barrier modules) |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2099-9767
Single action manual fire alarm station for hazardous areas, used on initiating device circuits protected by a Simplex 2081-9062 or 2081-9063 intrinsically safe barrier module. A firm downward pull breaks the plastic rod and operates the alarm switch. To reset, a key unlocks and opens the station, and a used break-rod must be replaced.
Intrinsically safe circuits are for indoor use only and must not share cable, conduit or raceway with other circuits.
Specifications
| Operation | Single action |
|---|---|
| Wiring | 18 AWG minimum, 14 AWG maximum (0.82 mm², 2.08 mm²) |
| Surface mounting | 2975-9178 red steel back box or 2975-9022 aluminum back box; box depth not less than 2 3/16 in. (56 mm) |
| Semi-flush mounting | Standard single gang 2 1/2 in. (64 mm) deep switch box, not recessed |
| Flush mounting | Flush mount adapter kit 2099-9819 (black) or 2099-9820 (beige) |
Used with
- 2081-9062 – Single channel intrinsically safe barrier module
- 2081-9063 – Dual channel intrinsically safe barrier module
- 2975-9178 – Surface mount steel box, red
- 2099-9819 – Flush mount adapter kit, black
- 2099-9804 – Replacement break-rod
From Simplex datasheet S2081-0018. The datasheet can be downloaded under Documents above.