Product details
| Part number | 2081-9063 |
|---|---|
| Description | Barrier 2 Ckt, KFDO-CS-EX2.51P |
| Category | Enclosures, Doors & Accessories / EOL, Surge, Barriers & Small Parts |
| System | Simplex fire alarm systems |
| Works with | 4004 and 4005 Class B IDCs, 4020 Class B IDCs, 4100 Class B IDC module 4100-5004, ZAM 4090-9101 (MAPNET II or IDNet), ZAMs 2190-9155 / 2190-9156 (MAPNET II) |
| Approvals | FM approved (intrinsically safe application) |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2081-9063
Dual channel, transformer-isolated intrinsically safe barrier module for Simplex initiating device circuits. It limits the circuit current below the ignition level so the wiring can run into hazardous locations of NEC Classes I, II and III, Divisions 1 and 2, Groups A to G. Each module needs a 2081-9061 installation kit and a 2975-9218 cabinet.
Intrinsically safe circuits are for indoor use only, cannot be used with alarm verification, and must not share cable, conduit or raceway with other circuits.
Specifications
| Input voltage (Vin) | 4 VDC to 35 VDC |
|---|---|
| Input current (Iin) | 40 mA maximum, limited by module impedance |
| Output current | Transfer current ≤ 40 mA; short circuit current ≤ 65 mA |
| Operating temperature | 32°F to 120°F (0°C to 49°C) |
| Operating humidity | Up to 85% RH maximum @ 86°F (30°C) |
| Dimensions | 4 1/2 in. H x 4 1/4 in. W (including terminal block) x 13/16 in. D (114 mm x 108 mm x 21 mm) |
| Entity parameters, Groups A, B | 0.14 μF; 3.84 mH; VOC 28.4 V; ISC 97 mA |
| Maximum line resistance | 10 Ω, fire alarm panel to last device in the hazardous location |
Used with
- 2081-9061 – Intrinsically safe barrier installation kit (required)
- 2975-9218 – Intrinsically safe barrier cabinet (required)
- 2099-9767 – Intrinsically safe single action manual station
- 2099-9799 – Intrinsically safe double action (breakglass) manual station
From Simplex datasheet S2081-0018. The datasheet can be downloaded under Documents above.