Product details
| Part number | 4007-9401 |
|---|---|
| Description | 4007ESMX, IDNAC, Red |
| Category | Fire Alarm Control Panels / 4007ES Panels |
| System | Simplex 4007ES fire alarm panels |
| Works with | MX Digital, IDNAC (TrueAlert ES, TrueAlert), ES Net, 4120 network |
| Approvals | UL listed (UL 864) |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4007-9401
Red 4007ES fire alarm control unit with MX Digital addressable communications for 250 points and a 3 A Class B IDNAC SLC for up to 127 addressable notification appliances. The IDNAC output holds 29 VDC in alarm, also on battery, for TrueAlert ES and TrueAlert appliances. The platinum version is 4007-9402.
Standby and alarm currents exclude appliance, point and circuit loads; add optional module and other currents separately for battery calculations.
Specifications
| Addressable capacity | MX Digital communications for 250 addressable points |
|---|---|
| IDNAC SLC | 3 A, regulated 29 VDC during Alarm, 127 addresses, 139 unit loads |
| Power supply | 4 A output power supply/battery charger |
| Standby / alarm current | 190 mA / 290 mA |
| Input power | 120 VAC input 2 A maximum @ 102 VAC to 132 VAC, 50/60 Hz; 240 VAC input 1 A maximum @ 204 VAC to 264 VAC, 50/60 Hz |
| Battery charging | 6.2 Ah up to 33 Ah |
| Display | 4.3 in. (109 mm) diagonal color touchscreen |
| Operating temperature | 32°F to 120°F (0°C to 49°C) |
Used with
- 4007-6312 – ESMX loop mezzanine card
- 4007-9804 – Dual Class A IDNAC Isolator (DCAI)
- 4007-9806 – SDACT module
- 4007-9801 – Eight point zone/relay module
- 4009-9801 – External battery cabinet
From Simplex datasheet S4007-0004. The datasheet can be downloaded under Documents above.