Product details
| Part number | 4007-9801 |
|---|---|
| Description | Zone-Relay Module |
| Category | Panel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards |
| System | Simplex 4007ES fire alarm panels |
| Works with | 4007ES, 4017ES |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4007-9801
Eight-point module for 4007ES and 4017ES control units; each point is set as a conventional IDC input or a relay output. It supports up to eight Class B IDCs or four Class A IDCs, up to eight relay outputs rated 2 A resistive at 30 VDC, or a mix. The 4007ES datasheets list one module as standard, with up to three more as options.
Class A IDCs need two points each, one out and one return.
Specifications
| Points | 8, each selectable as an IDC input or Relay output |
|---|---|
| IDCs | up to eight Class B IDCs, or up to four Class A IDCs |
| Relay outputs | up to eight relay outputs rated 2 A resistive at 30 VDC (N.O. or N.C.) |
| Devices per IDC | up to 30 two-wire devices |
| IDC EOL resistor values | 3.3 kohm, 2 kohm, 2.2 kohm, 3.4 kohm, 3.9 kohm, 4.7 kohm, 5.1 kohm, 5.6 kohm, 6.34/6.8 kohm, and 3.6 kohm + 1.1 kohm |
| Supervisory current | 83 mA max |
| Alarm current | 295 mA max |
| Installation instructions | 579-1103 |
Used with
- 4007-9802 – 25 VDC regulator module for zone/relay modules with devices needing nominal 25 VDC
- 4081-9002 – 3.3 kohm, 1 W EOL resistor for Class B initiating zones
From Simplex datasheet S4007-0001. The datasheet can be downloaded under Documents above.