Product details
| Part number | 4098-9733 |
|---|---|
| Description | SSD Heat Sensor |
| Category | Detectors & Bases / Smoke, Heat & Multi Sensors |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4100ES, 4010ES, 4007ES, 4010, 4100U, 4008 (reduced feature set), 4020 (MAPNET II), 4100 (MAPNET II), 4120 (MAPNET II), 2120 TrueAlarm CDT (MAPNET II) |
| Approvals | Heat sensors listed to UL 521 and ULC-S530; UL, ULC, CSFM listed; FM approved |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-9733
Self-restoring analog heat sensor head that mounts on a TrueAlarm sensor base and reports the local temperature to the fire alarm panel. The panel sets a fixed alarm temperature of 135°F or 155°F (57.2°C or 68°C), with or without rate-of-rise detection at 15°F or 20°F per minute. It can also be programmed as a utility sensor for 32°F to 155°F (0°C to 68°C) to give freeze warnings or flag HVAC problems.
Smoke and toxic gas can reach hazardous levels before a heat sensor alarms; smoke detection is recommended where life safety is a factor.
Specifications
| Fixed temperature settings | 135°F or 155°F (57.2°C or 68°C) |
|---|---|
| Rate-of-rise | 15°F or 20°F, (8.3°C or 11.1°C) for each minute |
| UL and ULC spacing | 60 ft x 60 ft (18.3 m) at 135°F; 40 ft x 40 ft (12.2 m) at 155°F |
| FM spacing | 20 ft x 20 ft (6.1 m) for fixed temperature only, RTI = Quick; 50 ft x 50 ft (15.2 m) with either rate-of-rise selection, RTI = Ultra Fast |
| Utility temperature range | 32°F to 155°F (0°C to 68°C) |
| Operating temperature range | 32°F to 122°F, 0°C to 50°C |
| Humidity range | 10% to 95% RH |
| Color | White (black version: 4098-9778) |
Used with
- 4098-9792 – Standard sensor base, white
- 4098-9789 – Sensor base with connections for remote LED alarm indicator or unsupervised relay
- 4098-9791 – Four-wire supervised relay base (not compatible with 2120 CDT)
- 4098-9780 – Two-wire supervised relay base (not compatible with 2120 CDT)
- 4098-9832 – Adapter plate for surface or semi-flush 4 in. square box and surface 4 in. octagonal box
From Simplex datasheet S4098-0019. The datasheet and UL listing can be downloaded under Documents above.