Product details
| Part number | 4090-5204 |
|---|---|
| Description | Signal IAM |
| Category | Addressable Modules & Interfaces / Addressable Modules (IAM/ZAM/Isolators) |
| System | Simplex fire alarm systems |
| Works with | 4100ES with MX Loop Module, 4010ES with MX Loop Module, 4100U with MX Loop Module |
| Approvals | UL listed to Standard 864 |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4090-5204
Addressable MX Technology module that provides a local notification appliance circuit (NAC) from a separately wired 24 VDC supply. It drives two Class B NACs or one Class A NAC, rated 2 A @ 24 VDC for up to 62 appliances. It can also provide a supervised output for other control applications.
Check the installation instructions for compatible notification appliances; a Class A output requires the 4081-9022 end-of-line resistor assembly.
Specifications
| NAC output | Two Class B NACs, or one Class A NAC, rated 2 A @ 24 VDC, up to 62 appliances |
|---|---|
| NAC power | Separately wired 24 VDC nominal input |
| MX Loop current | 1.1 mA in standby; 4.5 mA in alarm |
| Mounting box | Standard 2-gang MK box |
| Wiring connections | Terminal blocks, for wire size 20 to 14 AWG (0.5 to 2.5 mm²) |
| Operating temperature | 32° F to 120° F (0° C to 49° C) |
| Humidity | up to 93% RH at 90° F (32° C) |
Used with
- 4081-9022 – 27 kΩ end-of-line resistor harness, for Class A output
- 517.035.007 – Replacement module front cover
- 516.800.918 – MX Service Tool, ref. MX Model 801AP
From Simplex datasheet S4090-0012. The datasheet, UL listing and installation manual can be downloaded under Documents above.