Product details
| Part number | 2081-9048 |
|---|---|
| Description | Abort Supervision |
| Category | Addressable Modules & Interfaces / Addressable Modules (IAM/ZAM/Isolators) |
| System | Simplex fire alarm systems |
| Works with | 4004R |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2081-9048
Encapsulated 560 Ω, 1/2 W resistor module for a special purpose monitor (SPM) circuit of the 4004R suppression releasing panel in dual hazard applications. It allows non-current-limited abort switches and manual release stations to be on the same circuit.
In dual hazard systems each SPM with abort switches needs either a 1.2 kΩ, 1 W current limiting resistor or one Abort Supervision Module.
Specifications
| Resistance | 560 Ω, 1/2 W |
|---|---|
| Construction | Epoxy encapsulated |
| Dimensions | 1 3/8 in. W x 2 7/16 in. L x 1 1/16 in. H (34 mm x 62 mm x 27 mm) |
| Wiring | 18 AWG (0.82 mm²) wire leads, color coded |
Used with
- 2099-9149 – Double action manual release station
From Simplex datasheet S4004-0002. The datasheet can be downloaded under Documents above.