Product details
| Part number | 2099-9149 |
|---|---|
| Description | Double Act Pp Station with O Logo |
| Category | Manual Call Points & Release Stations / Manual Call Points / Pull Stations |
| System | Simplex fire alarm systems |
| Works with | 4004R |
| Approvals | UL listed to UL 38; ULC; CSFM; FM approved; MEA (NYC) acceptance |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2099-9149
Non-coded double action manual release station for suppression releasing systems: a spring-loaded plate marked PUSH is pushed back, then the lever is pulled. It has a normally open (NO) contact and a red housing with a white pull lever; the lever stays out after activation and is reset with a key. A release label kit is ordered separately.
Order label kit 4099-9802 separately to mark the release type (Clean Agent, Extinguishing, Carbon Dioxide, Foam System, Sprinkler or Manual).
Specifications
| Operation | Double action push and pull; normally open (NO) contact |
|---|---|
| Housing | Red with white raised lettering; Lexan polycarbonate or equal |
| Pull lever | White with red raised lettering |
| Housing dimensions | 5 in. H x 3 3/4 in. W x 1 in. D (127 mm x 95 mm x 25 mm) |
| Wire connections | Screw terminal for in/out wiring, for 18 AWG to 14 AWG wire (0.82 mm² to 2.08 mm²) |
| Temperature range | 32°F to 140°F (0°C to 60°C) intended for indoor operation |
| Humidity range | Up to 90% RH at 90°F (38°C) |
Used with
- 4099-9802 – Release label kit (required)
- 2975-9178 – Surface mount box, red steel
- 2975-9022 – Surface mount box, cast aluminum
- 2099-9804 – Replacement break-rod
- 252-019 – B key for manual station reset
From Simplex datasheet S2099-0010. The datasheet can be downloaded under Documents above.