Product details
| Part number | 4098-9774 |
|---|---|
| Description | SSD Photoelectric Sensor Black |
| Category | Detectors & Bases / Smoke, Heat & Multi Sensors |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | IDNet (4100ES, 4100U, 4010ES, 4010, 4007ES), MAPNET II (4020, 4100, 4120, 2120 TrueAlarm CDT) |
| Approvals | UL listed to UL 268 7th Edition; ULC listed to ULC-S529; CSFM; FM approved |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-9774
Black version of the TrueAlarm analog photoelectric smoke sensor. It sends its analog smoke reading to the fire alarm control unit, which sets the alarm sensitivity for each sensor and compensates for dust and dirt. It fits the TrueAlarm sensor bases, including the black 4098-9775 and 4098-9776 bases.
Fixed sensitivity settings higher than 1.0% per foot are not UL 268 7th Edition compliant.
Specifications
| Color | Black |
|---|---|
| Standard sensitivity | 1.25% to 3.1% for each foot |
| Special application sensitivities | 0.2%, 0.5%, and 1% for each foot |
| Communications | IDNet or MAPNET II communications, auto-selected, one address for each base |
| UL listed operating temperature range | 32°F to 100°F, 0°C to 38°C |
| Humidity range | 10% to 95% RH |
| Enclosure rating | NEMA 1 |
Used with
- 4098-9776 – Standard sensor base, black
- 4098-9775 – Sensor base with connections, black
- 4098-9792 – Standard sensor base, white
- 4098-9789 – Sensor base with connections, white
- 2098-9808 – Remote red LED alarm indicator
From Simplex datasheet S4098-0019. The datasheet and UL listing can be downloaded under Documents above.