Signal IAM

361.10 SAR 361.10 SAR

361.10 SAR incl. VAT
  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number4090-5204
DescriptionSignal IAM
CategoryAddressable Modules & Interfaces / Addressable Modules (IAM/ZAM/Isolators)
System Simplex fire alarm systems
Works with4100ES with MX Loop Module, 4010ES with MX Loop Module, 4100U with MX Loop Module
ApprovalsUL listed to Standard 864
AvailabilityOn request, ask for lead time
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4090-5204

Addressable MX Technology module that provides a local notification appliance circuit (NAC) from a separately wired 24 VDC supply. It drives two Class B NACs or one Class A NAC, rated 2 A @ 24 VDC for up to 62 appliances. It can also provide a supervised output for other control applications.

Check the installation instructions for compatible notification appliances; a Class A output requires the 4081-9022 end-of-line resistor assembly.

Specifications

NAC outputTwo Class B NACs, or one Class A NAC, rated 2 A @ 24 VDC, up to 62 appliances
NAC powerSeparately wired 24 VDC nominal input
MX Loop current1.1 mA in standby; 4.5 mA in alarm
Mounting boxStandard 2-gang MK box
Wiring connectionsTerminal blocks, for wire size 20 to 14 AWG (0.5 to 2.5 mm²)
Operating temperature32° F to 120° F (0° C to 49° C)
Humidityup to 93% RH at 90° F (32° C)

Used with

  • 4081-9022 – 27 kΩ end-of-line resistor harness, for Class A output
  • 517.035.007 – Replacement module front cover
  • 516.800.918 – MX Service Tool, ref. MX Model 801AP

From Simplex datasheet S4090-0012. The datasheet, UL listing and installation manual can be downloaded under Documents above.