Product details
| Part number | 2099-9799 |
|---|---|
| Description | Pull Station D/A Intrin Safe |
| Category | Manual Call Points & Release Stations / Manual Call Points / Pull Stations |
| System | Simplex fire alarm systems |
| Works with | Simplex intrinsically safe barrier modules 2081-9062 / 2081-9063 |
| Approvals | FM approved as intrinsically safe (with Simplex barrier modules) |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2099-9799
Double action breakglass manual fire alarm station for hazardous areas, used on initiating device circuits protected by a Simplex 2081-9062 or 2081-9063 intrinsically safe barrier module. The user throws the hammer against the glass window to expose the recessed pull lever, then pulls it to lock in the alarm switch. To reset, the station is unlocked with a key and the glass window is replaced.
Intrinsically safe circuits are for indoor use only and must not share cable, conduit or raceway with other circuits.
Specifications
| Operation | Double action (breakglass) |
|---|---|
| Wiring | 18 AWG minimum, 14 AWG maximum (0.82 mm², 2.08 mm²) |
| Surface mounting | 2975-9178 red steel back box or 2975-9022 aluminum back box; box depth not less than 2 3/16 in. (56 mm) |
| Semi-flush mounting | Standard single gang 2 1/2 in. (64 mm) deep switch box, not recessed |
| Flush mounting | Flush mount adapter kit 2099-9819 (black) or 2099-9820 (beige) |
Used with
- 2081-9062 – Single channel intrinsically safe barrier module
- 2081-9063 – Dual channel intrinsically safe barrier module
- 2975-9178 – Surface mount steel box, red
- 2099-9803 – Replacement breakglass
- 2099-9819 – Flush mount adapter kit, black
From Simplex datasheet S2081-0018. The datasheet can be downloaded under Documents above.