Simplex TrueAlarm detector heads are analog: the head reports its reading to the fire alarm panel, and the panel decides when to alarm and compensates for dust and dirt. The three heads we sell most are a photoelectric smoke sensor, a heat sensor and a multi-sensor. All three are sold without a base.
Photoelectric smoke sensor – 4098-9714
A pulsed LED light source and a silicon photodiode receiver, with 360° smoke entry and built-in insect screens. The panel sets the sensitivity: 1.25% to 3.1% per foot as standard, or 0.2%, 0.5% or 1% per foot for special applications. Its UL listed operating range is 0°C to 38°C, and it is rated for air velocities up to 1,220 m/min. Fixed settings higher than 1.0% per foot are not UL 268 7th Edition compliant.
Heat sensor – 4098-9733
A self-restoring heat sensor. The panel sets a fixed alarm temperature of 57.2°C or 68°C (135°F or 155°F), with or without rate-of-rise detection at 8.3°C or 11.1°C per minute. UL and ULC spacing is 18.3 m × 18.3 m at 135°F and 12.2 m × 12.2 m at 155°F. It can also run as a utility sensor from 0°C to 68°C, for example to give freeze warnings or flag HVAC problems. The datasheet is clear that smoke and toxic gas can reach hazardous levels before a heat sensor alarms, so smoke detection is recommended wherever life safety is a factor.
Multi-sensor – 4098-9754
A photoelectric smoke sensor and a thermistor heat sensor in one housing, using one IDNet address. The panel alarms on smoke, on heat, or on the TrueSense correlation of the two. Smoke sensitivity is set at the panel from 0.2% to 3.7% per foot; the heat part alarms at a fixed 57.2°C and/or on rate of rise. It works with the 4007ES, 4010ES, 4100ES and 4100U panels over IDNet.
The base
Each head needs a 4098 series base, ordered separately: the 4098-9792 standard base, the 4098-9789 base with connections for a remote LED or an unsupervised relay, the 4098-9793 isolator base or the 4098-9794 sounder base. The 4098-9832 adapter plate is for surface or semi-flush 4-inch square boxes.
Each product page has the full specifications and the datasheet and UL listing to download.