Product details
| Part number | VEP-A00-1P |
|---|---|
| Description | VEP with LEDs 1-PIPE |
| Category | Detectors & Bases / Aspirating & Duct Sampling |
| System | Fire alarm systems |
| Works with | 4100ES, 4010ES and 4007ES (IDNet, system firmware 6.02.02 or higher) |
| Approvals | UL, ULC and CSFM listed |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the VEP-A00-1P
VESDA-E VEP aspirating smoke detector with one sampling pipe and LED status indicators, using the Flair detection chamber. Simplex supplies it as 4098-VEP-A00-1P with onboard IDNet communications, so it connects directly to the IDNet loop of 4007ES, 4010ES and 4100ES panels and reports four alarm levels (alert, action, fire 1, fire 2), faults and smoke readings. It covers up to 10,764 sq. ft. (1,000 m²) with up to 427 ft (130 m) of branched pipe.
Set the IDNet base address with the Xtralis VSC software.
Specifications
| Supply voltage | 18 VDC to 30 VDC (24 V nominal) |
|---|---|
| Current at 24 VDC | 0.34 A quiescent, 0.37 A in alarm |
| Area coverage | 10,764 sq. ft. (1,000 m²) |
| Pipe length | 312 ft (95 m) linear; 427 ft (130 m) branched |
| Sampling holes | 22 |
| Relays | Seven pre-configured relays, contacts rated 2 A at 30 VDC (resistive) |
| Operating ambient | 32°F to 100°F (0°C to 38°C) |
| Dimensions (W x H x D) | 13.8 in. x 8.9 in. x 5.3 in. (350 mm x 225 mm x 135 mm) |
Used with
- VSP-960 – VESDA-E mounting bracket
- VSP-961 – VESDA-E exhaust adaptor US
- VSP-962 – VESDA-E filter
- VSP-963 – VESDA-E aspirator
From Simplex datasheet S4098-0056. The datasheet can be downloaded under Documents above.