Class B Mother Board

409.40 SAR 409.40 SAR

409.40 SAR incl. VAT
  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number562-856
DescriptionClass B Mother Board
CategoryReplacement PCBs / PCB Assemblies
System Simplex fire alarm systems
Works with4100 (2975-91xx back boxes), 4100U/4100ES (2975-94xx back boxes)
AvailabilityOn request, ask for lead time
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 562-856

Motherboard assembly 562-856 used in Simplex 4100 series 8-zone Class B zone modules. Simplex zone module instructions show it in the Class B monitor zone wiring and in the security wiring of the 4100/4120-5004 and 4100-5005 modules. The field wiring of the eight zones connects to its terminal blocks, and the zone daughter card plugs into the connector in its center.

The 4081-9002 EOL harness, not the 378-017 resistor, is required at the last device of each Class B zone.

Specifications

Zones8 Zone Class B
EOL at last device4081-9002 EOL Resistor Harness (3.3 K, 1W)
Unused zone3.3 K, 1 W resistor (378-017) across zone terminals
Security zone EOL (5004/5005)378-090 EOL Resistor (8.2 K, ½ W)
Max line resistance, contacts only800 Ohms
Standby voltage range at detector16.5 to 32 VDC
Wiring18 AWG, twisted/shielded pair

Used with

  • 4100-5004 – 8 zone Class B module, fire or security devices (4100 back boxes)
  • 4100-5005 – 8 zone Class B module, fire or security devices (4100U/4100ES back boxes)
  • 4081-9002 – EOL resistor harness, 3.3 K, 1 W
  • 733-525 – Power and communication harness

From Simplex installation guide 579-205. The installation manual can be downloaded under Documents above.