Product details
| Part number | 4100-3110 |
|---|---|
| Description | IDNET2 Module 250PT 4 Loop Isolator |
| Category | Panel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES (IDNet 2) |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-3110
IDNet 2+2 addressable interface module for the 4100ES panel with 250 point capacity. Its electrically isolated output has four short circuit isolating loops, each wired Class B or Class A, and it takes one block. It works with IDNet communicating devices and TrueAlarm sensors.
Mount it in an expansion bay or an available Master Controller bay module location; it cannot be mounted on the ES power supply.
Specifications
| Capacity | 250 points |
|---|---|
| Output loops | Four short circuit isolating Class B or Class A output loops |
| Size | 1 block |
| Standby / alarm current, no devices | 50 mA / 60 mA |
| Standby / alarm current, 250 devices | 250 mA / 350 mA |
| Wire type, new installation | Unshielded twisted pair (UTP) |
| Total wire length with T-taps (Class B) | Up to 12,500 ft (3.8 km), 0.60 μF |
| Maximum distance to device | 4000 ft (1219 m), 50 ohms (1 to 125 devices); 2500 ft (762 m), 35 ohms (126 to 250 devices) |
From Simplex datasheet S4100-1031. The datasheet can be downloaded under Documents above.