Skip to Content
Part no. 4100-3109

IDNET2 Module 250PT 2 Loop Isolator

990.15 SAR 990.15 SAR

  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number4100-3109
DescriptionIDNET2 Module 250PT 2 Loop Isolator
CategoryPanel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards
System Simplex 4100ES fire alarm panels
Works with4100ES (ES-PS), IDNet 2 devices and TrueAlarm sensors
AvailabilityIn stock in Riyadh
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4100-3109

Addressable IDNet 2 channel module for the 4100ES, with an electrically isolated output and two short circuit isolating loops wired Class B or Class A for up to 250 points. It supports IDNet devices and TrueAlarm sensors, including QuickConnect and QuickConnect2, and is standard on the ES-PS with IDNet 2 module.

A maximum of 20 devices with LED on is supported for each channel.

Specifications

Capacity250 points
OutputElectrically isolated, two short circuit isolating Class B or Class A loops
Size1 block
Current, no devices50 mA standby; 60 mA alarm
Current, 250 devices250 mA standby; 350 mA alarm (includes 20 device LEDs in alarm)
Distance from panel1 to 125 devices: 4000 ft (1219 m), 50 ohms; 126 to 250 devices: 2500 ft (762 m), 35 ohms
Total wire length with T-tapsUp to 12,500 ft (3.8 km), 0.60 μF
WireUnshielded twisted pair (UTP) for new installation; terminals for 18 to 12 AWG

Used with

  • 4100-3111 – IDNet Short Circuit Isolating Loop Output Module (up to two per 4100-3109)
  • 4100-3110 – IDNet 2+2 Module, four isolating loops

From Simplex datasheet S4100-1031. The datasheet can be downloaded under Documents above.