Product details
| Part number | 4100-6103 |
|---|---|
| Description | Dual Class A Isolator - IDNAC |
| Category | Panel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES, IDNAC SLC |
| Approvals | UL, ULC, CSFM listed; FM approved |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-6103
Module for 4100ES panels that converts one Class B IDNAC SLC input into two Class A SLC outputs, with short circuit isolation between each output. It is used to build Class A addressable notification loops for TrueAlert appliances. It takes one block of space.
The total current of both Class A outputs stays limited to the 3 A rating of the Class B input IDNAC SLC.
Specifications
| Size | 1 Block |
|---|---|
| Current (supv. / alarm) | 8.3 mA / 18.5 mA |
| Outputs | Two Class A SLC outputs from one Class B IDNAC SLC input |
| Addresses | Each isolated output SLC used requires one IDNAC address |
| Loop capacity | Each isolated loop supports up to 30 device addresses |
| Maximum quantity | Up to two DCAI Modules for each IDNAC SLC input, maximum of 6 DCAI Modules for each IDNAC SLC |
Used with
- 4100-5451 – IDNAC addressable notification SLC module
- 4100-5401 – ES-PS power supply
- 4905-9929 – TrueAlert Addressable Isolator+ Module
From Simplex datasheet S2080-0091. The datasheet can be downloaded under Documents above.