Product details
| Part number | 4100-5451 |
|---|---|
| Description | IDNAC Card |
| Category | Panel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES (IDNAC), TrueAlert ES addressable appliances, TrueAlert addressable appliances, 4009 IDNAC Repeater |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-5451
Addressable notification module for the 4100ES that provides three 3 A IDNAC signaling line circuits (SLCs). It works with TrueAlert ES and TrueAlert addressable notification appliances and with remote 4009 IDNAC Repeaters. It takes two blocks and mounts only on an ES power supply.
The 4100-5451 can only be powered from a 4100-5401 or 4100-5402 power supply.
Specifications
| Outputs | Three 3 A addressable SLCs |
|---|---|
| Size | 2 blocks, only on ES Power Supply |
| Max load, special application, on ES-PS / ES-XPS | 3.0 A / NAC, 9.0 A / Card |
| Current draw (supv. / alarm) | 124 mA / 230 mA |
| SLC capacity | Up to 127 addresses and up to 139 unit loads |
| Wire type | Unshielded twisted pair (UTP) |
| Max. wire length with T-taps (Class B), each SLC | 10,000 ft (3048 m) |
| Max. wire length, each SLC to any appliance | 4000 ft (1219 m) |
Used with
- 4100-5401 – ES-PS power supply
- 4100-5402 – ES-XPS power supply
- 4100-6103 – Dual Class A IDNAC Isolator (DCAI)
- 4100-5131 – ES-PS fan module
From Simplex datasheet S4100-1031. The datasheet can be downloaded under Documents above.