Product details
| Part number | 4100-5450 |
|---|---|
| Description | NAC Card |
| Category | Panel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES (ES-PS / ES-XPS) |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-5450
Conventional notification appliance circuit (NAC) module for the 4100ES with three outputs. Each output can be set as a Class B or Class A conventional NAC or as an auxiliary power output. The NACs support synchronized strobe or SmartSync horn/strobe operation over two wires.
The 4100-5450 can only be powered from a 4100-5401 or 4100-5402 power supply.
Specifications
| Outputs | Three 3 A NACs |
|---|---|
| Size | 1 block |
| Max load, special application, on ES-PS / ES-XPS | 3.0 A / NAC, 9.0 A / Card |
| Max load, special application, in bay | 3.0 A / NAC, 6.0 A / Card |
| Max load, regulated 24 V, on ES-PS / ES-XPS | 2.0 A / NAC, 5.0 A / Card |
| Max load, regulated 24 V, in bay | 2.0 A / NAC, 2.0 A / Card |
| Current draw (supv. / alarm) | 66 mA / 66 mA |
| Auxiliary power outputs | 3 A continuous duty |
Used with
From Simplex datasheet S4100-1031. The datasheet can be downloaded under Documents above.