Product details
| Part number | 4100-3120 |
|---|---|
| Description | Master Ctlr Esmxloop Factory Pid |
| Category | Panel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES with ES-PS power supplies, MX Technology addressable devices |
| Approvals | UL listed to UL 864 |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-3120
MX loop module supplied as a factory Master Controller feature selection for 4100ES panels; on international orders it can take the place of the IDNet 2 module (4100-3117). It is the same module, with the same specifications, as the 4100-6311 ESMX Loop Interface Module, which connects up to 250 MX addressable devices on dual isolated Class B loops that can be joined for Class A operation.
Specifications
| Addresses per loop | 250 maximum |
|---|---|
| MX loop output | 40 VDC maximum, 1 A maximum |
| Loop distance | 6560 ft (2000 m) typical maximum |
| Loop resistance | 150 ohm maximum |
| Module voltage | 24 VDC nominal, supplied from control panel power supply |
| Module current | 118 mA for module only, no devices |
| Mounting | One 5 in. x 4 in. block |
| Operating temperature | 32°F to 120°F (0°C to 49°C) |
Used with
- 4100-6312 – ESMX optional loop mezzanine card, adds a second loop
- 4100-5130 – Voltage regulator module, 25 VDC, for conventional devices on Monitor ZAMs
From Simplex datasheet S4100-1031. The datasheet can be downloaded under Documents above.