Product details
| Part number | 4100-3102 |
|---|---|
| Description | MAPNET Module Up to 127 Pts |
| Category | Panel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES, MAPNET II |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-3102
A 4100ES interface module that adds one MAPNET II addressable signaling line circuit with capacity for 127 points. Devices are ordered separately. The module takes 2 slots.
Specifications
| Capacity | 127 point |
|---|---|
| Module size | 2 Slots |
| Loading per MAPNET II device | 1.7 mA |
| Current, module without devices | 255 mA supervisory; 275 mA alarm |
| Current, fully loaded module | 471 mA supervisory; 491 mA alarm |
| Wire type | Shielded twisted pair (STP), new installation |
| Total wire length with T-taps (Class B) | Up to 10,000 ft (3 km); 0.58 μF |
Used with
- 4100-3103 – MAPNET II Isolator Module, four isolated outputs
From Simplex datasheet S4100-1031. The datasheet can be downloaded under Documents above.