Product details
| Part number | 4100-1290 |
|---|---|
| Description | 24 Point I/O Module |
| Category | Panel Cards & Modules / I/O, LED & Switch Modules |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES |
| Approvals | UL, ULC, CSFM listed; FM approved; UL 864 |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-1290
Panel module with 24 points for external connections; each point is set as a switch input (momentary or maintained) or as a lamp/relay driver output. Outputs can be steady or pulsing to drive remote relays, incandescent lamps or LEDs. It takes one 2 in. slot in a 4100ES panel bay and also provides the control connections for the 4003-9803 remote microphone.
Add the output currents separately to the module current for power and battery calculations.
Specifications
| Points | 24, each selectable as input or output |
|---|---|
| Size | 2" (51 mm) wide, 1 Slot |
| Module current | Supervisory = 34 mA; Alarm = 75 mA (add output currents separately) |
| Switch inputs | Momentary or maintained, 2 or 3 position; max. distance is 2500 ft (762 m) or 65 Ω |
| Output current | 150 mA @ 24 VDC per point; inrush current is limited for use with incandescent bulbs |
| Output distance | max. distance is 600 ft (183 m) or 2 Ω |
| Operating temperature | 32 °F to 120 °F (0 °C to 49 °C) |
| Operating humidity | Up to 93% RH, non-condensing @ 90 °F (32 °C) maximum |
Used with
- 4003-9803 – Remote microphone (its control wiring connects to this module)
From Simplex datasheet S4100-0032. The datasheet can be downloaded under Documents above.