Skip to Content
Part no. 4010-9929

IDNET2 Module 250POINT 4 Loop Isolator

1,541.00 SAR 1,541.00 SAR

  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number4010-9929
DescriptionIDNET2 Module 250POINT 4 Loop Isolator
CategoryPanel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards
System Simplex 4010ES fire alarm panels
Works with4010ES, IDNet devices and TrueAlarm sensors
AvailabilityIn stock in Riyadh
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4010-9929

Addressable channel module for 4010ES control units that adds a 250-point IDNet 2+2 signaling line circuit. Its electrically isolated output has four short circuit isolating loops, each wired Class A or Class B, for IDNet devices and TrueAlarm sensors. It mounts in one option block, up to three per panel.

A 1-bay 4010ES has only three option block spaces in total, so more modules need a 2-bay cabinet.

Specifications

Capacity250 point
Outputelectrically isolated output with four short circuit isolating Class B or Class A output loops
Current, no devices (Supv. / Alarm)50 mA / 60 mA
Current, 250 devices (Supv. / Alarm)250 mA / 350 mA
Option block usage1 block (3 max)
Card address consumption1
Maximum wiring distance0 to 125 devices: 4000 ft (1219 m); 126 to 250 devices: 2500 ft (762 m)
Wire connectionsTerminals for 18 to 12 AWG

From Simplex datasheet S4010-0004. The datasheet can be downloaded under Documents above.