Product details
| Part number | 4004-9860 |
|---|---|
| Description | 4PT Auxiliary Relay Module |
| Category | Panel Cards & Modules / Loop, Zone, NAC, Relay & CPU Cards |
| System | Simplex fire alarm systems |
| Works with | 4004R |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4004-9860
Expansion module for the 4004R suppression releasing panel that adds four auxiliary relays, each with two outputs selectable as N.O. or N.C. Relay 1 signals trouble, and relays 2 to 4 follow alarm, pressure/waterflow/release timer and release events of their hazard; a switch on the module disconnects relays 2 to 4. Dual hazard systems need two modules.
Relay outputs must be connected to a 15 A maximum circuit breaker.
Specifications
| Relays | Four relays with two outputs per relay; individually selectable as N.O. or N.C. |
|---|---|
| AC rating | 7 A at 120 VAC, resistive |
| DC rating | 5 A at 30 VDC, 0.35 power factor, inductive |
| Module current | 12 mA standby; 70 mA with all four relays energized; at 24 VDC |
| Contacts | Unsupervised |
| Wiring | Terminals rated for 18 AWG to 12 AWG (0.82 mm² to 3.31 mm²) |
| Maximum per panel | Two |
From Simplex datasheet S4004-0002. The datasheet can be downloaded under Documents above.