Part number4906-9131
DescriptionWeatherproof Multi-Candela Horn/Strobe Non-Addressable Wall Mt Red
CategoryNotification Appliances / Conventional Horns, Strobes & Speakers
System Simplex TrueAlarm detectors and TrueAlert appliances
Works with4100ES (SmartSync), 4100U (SmartSync), 4010ES (SmartSync), 4010 (SmartSync), 4007ES Hybrid (SmartSync), 4008 (SmartSync), 4006 (SmartSync), …
ApprovalsUL listed to UL 1971 (indoor) and UL 1638 (outdoor, WP75); CSFM (7125-0026:331); FM approved
AvailabilityIn stock in Riyadh
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 4906-9131

The 4906-9131 is a non-addressable wall mount horn/strobe (A/V) in a red NEMA 3R weatherproof housing with white FIRE lettering, for indoor or outdoor use. A plug sets the strobe for indoor use under UL 1971 to one of its multi-candela sets, 15/30/75 cd or 15/60/75 cd, or to WP75 (75 cd) for outdoor use under UL 1638; the factory setting is WP75. It runs on regulated 24 VDC and supports SmartSync two-wire control, which lets the horn be silenced while the strobe keeps flashing.

Mounting requires the matching red weatherproof box 49WPBB-AVVOWR, ordered separately.

Specifications

Strobe intensity, UL 1971 (indoor)15/30/75 cd or 15/60/75 cd (multi-candela sets)
Strobe intensity, UL 1638 (outdoor)75 cd (setting WP75)
Rated voltageRegulated 24 VDC (16 VDC to 33 VDC)
Max. RMS current, UL 197191 mA at 15 cd, 204 mA at 60 cd, 249 mA at 75 cd
Max. RMS current, WP75205 mA at 32°F to 150°F (0°C to 66°C); 277 mA at -31°F to below 32°F (-35°C to 0°C)
Horn output at 10 ft (3 m), 24 VDC, UL 464 reverberant83 dBA steady, 79 dBA coded
Temperature range32°F to 122°F (0°C to 50°C) UL 1971; -31°F to 150°F (-35°C to 66°C) UL 1638
EnclosureNEMA 3R, red housing, white FIRE lettering, clear lens

Used with

  • 49WPBB-AVVOWR – Red surface mount weatherproof box (required)
  • 4905-9938 – SmartSync Control Module
  • 4905-9914 – Synchronized flash module, Class B
  • 4905-9922 – Synchronized flash module, Class A
  • 4905-9833 – Red bilingual FEU/FIRE horn/strobe cover

From Simplex datasheet S4906-0010. The datasheet and UL listing can be downloaded under Documents above.