Product details
| Part number | 4190-6051 |
|---|---|
| Description | Ethernet Switch |
| Category | Network, Annunciators & Software / Network & Fiber Media Cards |
| System | Simplex 4100ES fire alarm panels |
| Works with | TrueSite Workstation, TrueSite Incident Commander |
| Approvals | UL 864 Recognized component (not agency listed for fire alarm) |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4190-6051
Eight-port wired Ethernet switch module for TrueSite Workstation and Incident Commander LANs where a fire alarm listing is not required. It is a UL 864 recognized component and does not include the earth detection module or cabinet of the listed Fire Alarm Ethernet Switches. It is powered from a 4190-6052 or 4190-6053 power adapter.
Not for fire alarm listed applications, because it has no earth detection module or cabinet.
Specifications
| Connections | Eight wired Ethernet connections |
|---|---|
| Power | 6 W @ 10-36 VDC; 6 VA @ 8-24 VAC |
| Dimensions | 5-11/16 in. x 7-3/8 in. x 1-3/4 in. (145 mm x 187 mm x 44.5 mm) |
| Listing status | UL 864 Recognized component; not agency listed for fire alarm |
Used with
- 4190-6052 – Wall mount power adapter, 120 VAC input
- 4190-6053 – Wall mount power adapter, 240 VAC input
- 4190-6050 – Listed Fire Alarm Ethernet Switch, eight wired ports (alternative)
From Simplex datasheet S4190-0018. The datasheet and installation manual can be downloaded under Documents above.