Product details
| Part number | 4606-9202 |
|---|---|
| Description | Color LCD Annunciator, Flush, Red |
| Category | Network, Annunciators & Software / Annunciators & Graphics |
| System | Simplex fire alarm systems |
| Works with | 4007ES (RUI) |
| Approvals | UL, ULC, CSFM listed (7300-0026:0382); FM approved; NYC Fire Dept approved (COA #6191A) |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4606-9202
Remote color touchscreen LCD annunciator with red trim for the 4007ES fire alarm panel. Its 4.3 inch display repeats panel status and point details away from the panel, with LEDs for alarm, priority 2, supervisory, trouble, alarm silenced and AC power, a tone-alert sounder, a keyswitch and three programmable switches. It talks to the panel over the RUI line on one unshielded twisted pair, needs separate 24 VDC power wiring, and flush mounts in a RACO 944 5-gang box; up to 6 can be used per 4007ES.
Where annunciator communications or power wiring leaves the building, suppression is required, including 2081-9044 overvoltage protectors on each end of the RUI wiring.
Specifications
| Display | 4.3” (109 mm) diagonal color touchscreen |
|---|---|
| Voltage | 18 to 32 VDC, system supplied |
| Current | Alarm 124 mA; Display Active 70 mA; Standby 45 mA |
| Communications | RUI (Remote Unit Interface); up to 6 Color Touchscreen LCD Annunciators per 4007ES |
| RUI wiring | Unshielded twisted pair (UTP), 18 AWG (0.82 mm²) for most applications; Class B T-tap up to 10,000 ft (3048 m) total, up to 2500 ft (762 m) to farthest device |
| Dimensions | 13” W x 5.21” H x 2” D (330 mm x 132 mm x 51 mm) |
| Flush mounting box | 5-gang masonry box, RACO # 944, 2 ½” (64 mm) deep or equal (supplied separately) |
| Operating temperature / humidity | 32° to 120° F (0° to 49° C); up to 93% RH, non-condensing at 100° F (38° C) |
Used with
- 2975-9461 – Red surface mount metal box
- 2975-9463 – Red semi-flush mount box adapter for existing 2-, 4-, 6-gang or 4 in. square flush boxes
- 2081-9044 – Overvoltage protector for RUI communications
- 2081-9028 – Isolated Loop Circuit Protector for 24 VDC power wiring above 200 mA
- RACO 944 – 5-gang box for flush mounting (supplied separately)
From Simplex datasheet S4606-0003. The datasheet, UL listing and installation manual can be downloaded under Documents above.