Product details
| Part number | 4100-6069 |
|---|---|
| Description | Bacpac Ethernet Module |
| Category | Network, Annunciators & Software / Network & Fiber Media Cards |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES, 4100U, 4100/4100+ and 4120 (legacy), BACnet IP / BACnet MS/TP, Modbus TCP / Modbus RTU, Metasys |
| Approvals | UL listed to UL 864; ULC listed to ULC-S527; CSFM |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-6069
Panel-mounted module that passes fire alarm system status from a Simplex control unit to a building automation system using BACnet (IP or MS/TP) or Modbus (TCP or RTU). It connects to port B of the panel's RS-232 module and outputs on Ethernet or RS-485. The 4100-6069 handles up to 1500 points and takes a single 2 in. slot.
The RS-232 module is ordered separately, and the Ethernet LAN cable is supplied separately.
Specifications
| Maximum points | 1500 |
|---|---|
| Protocols | BACnet IP, BACnet MS/TP, Modbus TCP, Modbus RTU |
| Input power | 24 VDC from FACU; operation range 9 VDC to 30 VDC |
| Current | 123 mA maximum from 24 VDC FACU supply |
| Module size | single slot (2 in.) module |
| Required RS-232 module | 4100-6038 (4100ES/4100U); 4100-0113 (4100/4100+/4120) |
| Operating temperature range | 32°F to 120°F (0°C to 49°C) |
| Humidity range | Up to 93% RH, non-condensing @ 90°F (32°C) maximum |
Used with
- 4100-6038 – RS-232 module for 4100ES and 4100U
- 4100-0113 – RS-232 module for 4100/4100+ and 4120
From Simplex datasheet S4100-0051. The datasheet and UL listing can be downloaded under Documents above.