Product details
| Part number | 4100-6056 |
|---|---|
| Description | Network Media Card Wired |
| Category | Network, Annunciators & Software / Network & Fiber Media Cards |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES, 4100U, Network System Integrator (NSI), 4120 network |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-6056
The 4100-6056 is the wired media card for 4120 fire alarm network communications on the 4100ES and 4100U, and is also used with the Network System Integrator. It mounts on the 4100-6078 or 4100-6061 modular network interface card. The wired module has isolated earth detection and electrical characteristics similar to RS-485.
Shielded cable and circuit protection is required when the network wiring leaves the building.
Specifications
| Mounts on | 4100-6078 or 4100-6061 modular network interface |
|---|---|
| Alarm/Supv. current | 55 mA |
| Distance, 18 AWG UTP | 17,000 ft (5.4 km) at 9600 baud; 10,000 ft (3 km) at 57.6 k |
| Distance, 24 AWG telephone cable UTP | 12,000 ft (3.65 km) at 9600 baud; 7,000 ft (2.13 km) at 57.6 k |
| 18 AWG cable | Unshielded Twisted Pair (UTP); maximum of 58 pF/ft, (190 pF/m) between conductors; shielded cable is allowed |
| Electrical | Electrical characteristics are similar to RS-485; provides isolated earth detection |
Used with
- 4100-6078 – Modular network interface for master controller
- 4100-6061 – Modular network interface for redundant master controller
From Simplex datasheet S4100-0056. The datasheet and UL listing can be downloaded under Documents above.