Product details
| Part number | 4010-9912 |
|---|---|
| Description | Serial DACT |
| Category | Network, Annunciators & Software / Communicators, DACT & Serial |
| System | Simplex 4010ES fire alarm panels |
| Works with | 4010ES |
| Approvals | UL 864 listed per NFPA 72 for Central Station Service; operation listed to UL Standard 1459; registered to FCC Part 68 |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4010-9912
Serial digital alarm communicating transmitter (SDACT) module that mounts inside the 4010ES panel. It reports alarms, troubles, supervisory conditions and point status to a central station over two telephone lines, up to ten events per call, in Contact ID (preferred), 3/1 or 4/2 pulse, BFSK or SIA format.
It must mount in block D under Main System Supply 2 and needs two data certified POTS telephone lines.
Specifications
| Mounting | Block D, top bay, under Main System Supply 2 (one block) |
|---|---|
| Voltage | 18-32 VDC, from panel |
| Current | Standby = 30 mA; Report Mode = 40 mA |
| Point capacity | 4000 points maximum |
| Telephone jack | RJ31X (2 required) |
| Connection type | Loop start, pulse or tone dialing; Data Certified POTS lines |
| Cable | 733-913 (2080-9047), 14 ft long (4.3 m), RJ-45 plug to spade lugs; included |
| Operating temperature | 32° F to 120° F (0° C to 49° C) |
Used with
- 2080-9047 – SDACT cable, 14 ft (4.3 m), RJ-45 plug to spade lugs (two included)
From Simplex datasheet S2080-0009. The datasheet can be downloaded under Documents above.