Product details
| Part number | 4007-9812 |
|---|---|
| Description | Dual RS232 Module |
| Category | Network, Annunciators & Software / Communicators, DACT & Serial |
| System | Simplex 4007ES fire alarm panels |
| Works with | 4007ES, Simplex remote printer, PC annunciator, Third-party interface (RS-232) |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4007-9812
The 4007-9812 is a Dual RS-232 Interface Module for the 4007ES fire alarm control unit. It gives the panel two RS-232 connections for a Simplex remote printer, a PC annunciator or a third-party interface. It mounts inside the 4007ES cabinet in module location E.
Location E takes one module: the 4007-9812, a 4007-9801 Zone/Relay Module, a 4007-9804 Dual Class A IDNAC Isolator or a 4007-9802 25 V Regulator Module.
Specifications
| Ports | Two ports/connections maximum |
|---|---|
| Supervisory current | 60 mA |
| Alarm current | 60 mA |
| Mounting location | Location E in the 4007ES cabinet |
| Host panel | 4007ES fire control unit |
Used with
From Simplex datasheet S4007-0002. The datasheet and UL listing can be downloaded under Documents above.