Product details
| Part number | 4007-9806 |
|---|---|
| Description | Sdact Module |
| Category | Network, Annunciators & Software / Communicators, DACT & Serial |
| System | Simplex 4007ES fire alarm panels |
| Works with | 4007ES |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4007-9806
Serial digital alarm communicator transmitter (SDACT) card that mounts inside a 4007ES panel. It reports events and changes of specific points to a central station over telephone lines. Each phone line connection needs one 2080-9047 DACT cable.
When a network card with fiber media cards is installed, the SDACT needs the 650-1838 flat mounting bracket, ordered separately.
Specifications
| Current (standby / alarm) | 30 mA / 40 mA |
|---|---|
| Connection cable | 2080-9047 DACT cable, 14 ft (4.3 m) long, RJ45 plug on one end, spade lugs on the other |
| Installation instructions | 579-954 |
Used with
- 2080-9047 – DACT cable, 14 ft (4.3 m), one per phone line
- 650-1838 – Flat mounting bracket
From Simplex datasheet S4007-0004. The datasheet can be downloaded under Documents above.