Part no. 2099-9103

Pull Station Break Glass in/O

225.40 SAR 225.40 SAR

225.40 SAR incl. VAT
  • Genuine manufacturer parts
  • Stock and delivery from Riyadh
  • Technical support from our engineers: +966 11 216 0987

Product details

Part number2099-9103
DescriptionPull Station Break Glass in/O
CategoryManual Call Points & Release Stations / Manual Call Points / Pull Stations
System Simplex fire alarm systems
ApprovalsUL listed to UL 38; ULC and CSFM listed; FM approved; MEA (NYC) accepted
AvailabilityOn request, ask for lead time
SupportSelection, compatibility and programming help from our engineers

Need it for a project?

Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.

About the 2099-9103

Non-addressable double action manual fire alarm station of the breakglass type, without annunciator contacts. The user strikes the front-mounted hammer to break the glass, then pulls the recessed lever, which latches in the alarm position. A key is needed to reset the station.

After operation, the station is reset with a key and the broken glass is replaced (2099-9803).

Specifications

OperationDouble action, break-glass (general alarm)
MountingSemi-flush: standard single gang switch box, 64 mm deep, not recessed; surface: Wiremold V5744S box
Wire connectionsScrew terminal for in/out wiring, for 18 AWG to 14 AWG wire
UL listed temperature range32°F to 120°F (0°C to 49°C) intended for indoor operation
Humidity rangeUp to 93% RH at 100°F (38°C)
HousingRed with white raised lettering; high impact polycarbonate
Housing dimensions5 in. H x 3 3/4 in. W x 1 in. D (127 mm x 95 mm x 25 mm)

Used with

  • 2099-9803 – Replacement breakglass
  • 2099-9822 – Replacement retaining clip for breakglass
  • 2099-9819 – Flush adapter kit, black
  • 252-019 – B key for manual station reset

From Simplex datasheet S2099-0007. The datasheet can be downloaded under Documents above.