Product details
| Part number | 2080-9060 |
|---|---|
| Description | Maintenance Switch with Lamp, Surface |
| Category | Manual Call Points & Release Stations / Abort & Maintenance Switches |
| System | Simplex fire alarm systems |
| Works with | Fire suppression system releasing appliance circuits (RACs) |
| Approvals | UL, ULC & CSFM listed; UL listed to Standard 864 |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2080-9060
The 2080-9060 is a keyswitch maintenance switch with disconnect indicator lamp, used to disconnect a fire suppression releasing appliance circuit (RAC) for service. In the disabled position it opens the output circuit and places a 16.2 kΩ resistor across the input circuit, so the host panel shows a supervisory condition. This surface mount model is on a double-gang stainless steel plate and comes with a red mounting box; the lamp needs a separate 24 VDC supply.
Not FM approved, and the indicator lamp needs separate 24 VDC wiring.
Specifications
| Mounting | Surface mount; includes red mounting box |
|---|---|
| Plate size | Double-gang stainless steel plate |
| Contact blocks | 3 position contact block housing with 2 contact blocks installed |
| Contact rating | Silver contacts; 1 normally open & 1 normally closed; rated 2 A resistive @ 30 VDC |
| Disabled position | Opens connection to output and places a 16.2 kΩ resistor across the input circuit |
| Indicator light | Replaceable 2 W incandescent bulb; 24 to 30 VDC typical; 83 mA @ 24 VDC; requires separate 24 VDC |
| Wiring | 18 AWG (0.82 mm²) color coded wire leads for suppression circuit; terminal blocks for lamp wiring |
| Temperature / humidity | 32° F to 120° F (0° C to 49° C); up to 93% at 90°F (32° C) |
Used with
- 2080-9061 – Additional contact block, 1 Form C contact
From Simplex datasheet S2080-0010. The datasheet and UL listing can be downloaded under Documents above.