Product details
| Part number | 4099-9015 |
|---|---|
| Description | Station-LED, Da Pp Add, NO Logo |
| Category | Manual Call Points & Release Stations / Manual Call Points / Pull Stations |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4100ES, 4010ES, 4010, Installed 4100, 4120 and 4020 systems, IDNet, MAPNET II |
| Approvals | UL listed to UL 38; ULC and CSFM listed; FM approved |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4099-9015
Addressable manual station for suppression releasing applications, with double action push-and-pull operation and a red housing. Power and data come over IDNet or MAPNET II on one wire pair; an LED flashes during communication and stays on when the station is activated. The releasing-type label (clean agent, CO2, foam, sprinkler and others) comes from the 4099-9802 kit, ordered separately.
The 4099-9802 label kit is required and ordered separately to mark the releasing application.
Specifications
| Operation | Double action, push and pull |
|---|---|
| Communications | IDNet or MAPNET II communications, 1 address per station |
| Address | Dipswitch, 8 position |
| Wire connections | 18 to 14 AWG |
| Housing | Red with white raised lettering; Lexan polycarbonate |
| Pull lever | White with red raised lettering |
| Dimensions | 5” H x 3 ¾” W x 1” D (127 mm x 95 mm x 25 mm) |
| Temperature | 32° to 120° F (0° to 49° C) intended for indoor operation |
Used with
- 4099-9802 – Releasing label kit (required)
- 2975-9178 – Red surface mount steel box
- 2975-9022 – Red cast aluminum surface mount box
- 2099-9819 – Flush mount adapter kit, black
- 2099-9804 – Replacement break-rod
From Simplex datasheet S4099-0006. The datasheet can be downloaded under Documents above.