Product details
| Part number | 2099-9754 |
|---|---|
| Description | Pull Station S/A, in/Out |
| Category | Manual Call Points & Release Stations / Manual Call Points / Pull Stations |
| System | Simplex fire alarm systems |
| Approvals | UL listed to UL 38; ULC; CSFM (7150-0026:175); FM approved; MEA (NYC) acceptance |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2099-9754
The 2099-9754 is a non-coded, non-addressable single action manual fire alarm station for general alarm. A firm downward pull operates the alarm switch and the lever stays latched out as a visible sign; resetting it needs a key. This basic model has no pre-signal, annunciator contacts or extra covers, and semi-flush mounts on a standard single gang switch box.
For semi-flush mounting do not recess the box; mount it flush or with 1/16 in. (2 mm) maximum protrusion.
Specifications
| Operation | Single action, general alarm |
|---|---|
| Wire connections | Screw terminal for in/out wiring, for 18 AWG to 14 AWG wire |
| UL listed temperature range | 32°F to 120°F (0°C to 49°C) intended for indoor operation |
| Humidity range | Up to 93% RH at 100°F (38°C) |
| Housing | Red with white raised lettering; high impact polycarbonate |
| Housing dimensions | 5 in. H x 3 3/4 in. W x 1 in. D (127 mm x 95 mm x 25 mm) |
| Mounting | Semi-flush on standard single gang (64 mm) deep switch box, or surface on Wiremold box V5744S |
Used with
- 252-019 – B key for manual station reset
- 2099-9804 – Replacement break-rod
- 4099-9805 – NO GRIP retrofit kit for single action stations
- 2099-9819 – Flush adapter kit, black
- 2099-9820 – Flush adapter kit, beige
From Simplex datasheet S2099-0007. The datasheet and UL listing can be downloaded under Documents above.