Product details
| Part number | 2099-9136 |
|---|---|
| Description | XAL-53 Explosion Proof Station |
| Category | Manual Call Points & Release Stations / Manual Call Points / Pull Stations |
| System | Simplex fire alarm systems |
| Approvals | UL, ULC and CSFM listed; CSA certified (agency listings by Killark) |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2099-9136
Non-coded double action manual fire alarm station for hazardous locations: lift the cover, then pull down the ring. It has a copper-free cast aluminum enclosure in red textured powder epoxy paint and one normally open plus one normally closed contact. It suits sites such as refineries, chemical plants, spray painting booths and storage areas.
Specifications
| Hazardous locations | Class I, Divisions 1 & 2, Groups C & D; Class II, Divisions 1 & 2, Groups E, F, & G; Class III, Divisions 1 & 2 |
|---|---|
| Contacts | 1 N.O., 1 N.C. |
| 120 VAC ratings | 6 A break, 720 VA; 10 A continuous carry |
| 125 VDC ratings | 1.1 A, make/break; 2.5 A continuous carry |
| Wire connections | Screw terminals for in/out wiring, 18 to 12 AWG wire (0.82 to 3.31 mm²) |
| Conduit openings | ¾” NPT feed through |
| Dimensions | 6 ⅜” H x 3” W x 4 ½” D (162 mm x 76 mm x 114 mm) |
| Housing | Copper-free, cast aluminum alloy; red textured powder epoxy paint |
From Simplex datasheet S2099-0008. The datasheet can be downloaded under Documents above.