Product details
| Part number | 4100-1241 |
|---|---|
| Description | Message Expansion, 8 Minutes |
| Category | Fire Fighter Telephones & Voice / Voice Evacuation Audio & Amplifiers |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES emergency voice/alarm, analog or digital audio |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-1241
Memory expansion module for 4100ES emergency voice/alarm audio controllers. It gives 8 minutes of recorded message storage at normal resolution, or 4 minutes at high resolution, and mounts to the audio controller module. It is used in analog or digital audio systems.
The 4100-1411 ES Net digital controller board has 32 minutes of message memory built in and does not need this expansion.
Specifications
| Message storage | 8 minutes at normal resolution or 4 minutes at high resolution |
|---|---|
| Supervisory current | 2 mA |
| Active current | 17 mA |
| Mounting | Mounts to audio controller module |
Used with
- 4100-1210 – Analog audio controller board
- 4100-1311 – Eight channel digital audio controller board
- 4100-1242 – 32 minute message expansion module (larger memory)
From Simplex datasheet S4100-1034. The datasheet can be downloaded under Documents above.