Product details
| Part number | 4100-1329 |
|---|---|
| Description | Dig. 100W Amplifier, 6NAC, 120VAC, 70V |
| Category | Fire Fighter Telephones & Voice / Voice Evacuation Audio & Amplifiers |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES (digital audio) |
| Approvals | UL |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-1329
Primary 100 W single channel amplifier with digital input for 4100ES emergency voice systems, with 70.7 VRMS output and a 120 VAC, 60 Hz supply. It has a built-in power supply, uses system battery backup and has six onboard Class B audio NACs. It is constant supervision compatible.
When used for paging or background music with constant supervision, output is derated to 70% of alarm power; full output is available for alarm.
Specifications
| Output | 70.7 VRMS, 100 W |
|---|---|
| Power supply input | 120 VAC, 60 Hz; 4 A maximum at 102 to 132 VAC |
| Audio NACs | Six, Class B audio NACs |
| NAC rating | 100 speakers maximum; 1.414 A @ 70.7 VRMS (100 W) |
| Supervisory current | 220 mA (digital) with power stage supervised |
| Alarm current at full output | 9.6 A with continuous horn tone; 3.8 A average, with temporal pattern horn |
| Mounting | Blocks E, F, G and H |
Used with
- 4100-1335 – Backup 100 W digital amplifier, 70.7 VRMS, 120 VAC
- 4100-1248 – 100 W amplifier expansion NAC module
- 4100-1249 – 100 W Class A adapter module
- 4100-1260 – Constant supervision adapter, 70.7 VRMS
- 4100-1311 – Eight channel digital controller board
From Simplex datasheet S4100-1034. The datasheet can be downloaded under Documents above.