Product details
| Part number | 4100-0625 |
|---|---|
| Description | Local Mode Tpr Interface |
| Category | Fire Fighter Telephones & Voice / Voice Evacuation Audio & Amplifiers |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES, 4100U |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-0625
Transponder Interface Card with local mode for 4100ES and 4100U MINIPLEX transponders. If communication with the master controller is lost, it controls the transponder cabinet: an alarm on any fire alarm input activates all alarm notification appliance circuits. It has a terminal block for an optional remote Local Mode Controller.
Local mode is limited to alarm functions; relays and other auxiliary control outputs do not activate.
Specifications
| Rated voltage | 24 VDC |
|---|---|
| Operating voltage | 18-33 VDC |
| Output voltage | 8 V @ 1 A; 100 mV p-p ripple |
| Input current | 38 mA maximum with no attachments (no 8V load), 82 mA maximum with local mode controller (no 8V load) |
| Local mode | General alarm only; relays and other auxiliary control outputs do not activate |
| Mounting | Block A |
| Operating temperature | 32° to 120° F (0° to 49° C) |
Used with
- 4601-9108 – Local Mode Controller, remote mounted (also 4601-9109, 4601-9110, 4601-9111; red or beige, flush or surface)
- 4100-0621 – Analog audio riser module
- 4100-0622 – Digital audio riser module
From Simplex document 579-160. The installation manual can be downloaded under Documents above.