Product details
| Part number | 4100-0621 |
|---|---|
| Description | Analog Audio Riser Module |
| Category | Fire Fighter Telephones & Voice / Voice Evacuation Audio & Amplifiers |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES, 4100U |
| Approvals | UL, ULC, CSFM listed; FM approved; OTCR/NYC approved |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-0621
Analog audio riser module for 4100ES/4100U MINIPLEX transponders and network nodes. It accepts one or two separate audio signals from the host control panel and is controlled by the Transponder Interface Module, which it connects to by ribbon cable. It takes one block and mounts in Block B.
A 4100ES audio system is either analog or digital, not mixed; this riser is for analog systems.
Specifications
| Channels | Two (dual channel) |
|---|---|
| Input voltage | 18-33 VDC |
| Size | 1 Block |
| Mounting | Block B |
| Analog riser distance | Up to 10,000 ft (3048 m) total with 18 AWG shielded twisted pair (STP) |
| Operating temperature | 32° to 120° F (0° to 49° C) |
| Humidity | Up to 93% relative humidity at 90° F (32° C) |
Used with
- 4100-0620 – Basic transponder interface card
- 4100-0625 – Local mode transponder interface card
- 4100-0623 – Network audio riser controller module
From Simplex datasheet S4100-1034. The datasheet and installation manual can be downloaded under Documents above.