Product details
| Part number | 4009-9602 |
|---|---|
| Description | IDNAC Repeater 120/240 Red |
| Category | Fire Alarm Control Panels / NAC Extenders & Repeaters |
| System | Simplex fire alarm systems |
| Works with | IDNAC SLC, TrueAlert ES and TrueAlert addressable notification appliances, 4007ES (IDNAC) |
| Approvals | UL, ULC, CSFM listed; FM approved; MEA (NYC) acceptance; listed to UL 864 and ULC S527 |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4009-9602
IDNAC repeater in a red cabinet. It takes an IDNAC SLC input and gives a repeated 3 A SLC output at 29 VDC to extend wiring distance and power for TrueAlert and TrueAlert ES addressable notification appliances. It adds up to 139 unit loads and has a 200 mA auxiliary output and a built-in battery charger; the platinum version is 4009-9601.
Each repeater uses one IDNAC address and does not add address capacity; a Class A output needs the 4009-9814 Class A Adapter.
Specifications
| Input voltage | 120 VAC, 50/60 Hz, or 220/230/240 VAC, 50/60 Hz, +10%, -15%, auto-select |
|---|---|
| IDNAC SLC output | 3 A maximum @ 29 VDC for Special Application appliances |
| Added capacity | up to 139 additional unit loads |
| IDNAC input | 1 address, 4 unit loads |
| Auxiliary output | 200 mA maximum |
| Standby / alarm current (panel) | 70 mA / 96 mA |
| Battery charging | up to 12.7 Ah batteries in cabinet; up to 25 Ah batteries with 4009-9801 external battery cabinet |
| Operating temperature | 32 °F to 120 °F (0 °C to 49 °C) |
Used with
- 4009-9814 – Class A Adapter Module
- 4009-9801 – External battery cabinet for 25 Ah batteries
- 4905-9929 – Remote TrueAlert Communications Isolator
- 2975-9812 – Red semi-flush box trim
From Simplex datasheet S4009-0004. The datasheet can be downloaded under Documents above.