Product details
| Part number | 4004-9302 |
|---|---|
| Description | 4004R Release Panel Red |
| Category | Fire Alarm Control Panels / Conventional & Releasing Panels |
| System | Simplex fire alarm systems |
| Works with | Simplex 4098-5601 to 4098-5613 photo, photo-heat and heat detectors (listed in the datasheet), … |
| Approvals | UL, ULC, FM, CSFM & MEA (NYC); listed to UL Standard 864 and ULC Standard S527; CSFM Listing 7165-0026:314 |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4004-9302
The 4004-9302 is the red version of the 4004R conventional releasing panel for automatic extinguishing agent release and for deluge and preaction sprinkler control. It has four IDCs, two NACs, two releasing appliance circuits (RACs), two special purpose monitor inputs for manual release/abort or waterflow/supervisory, and three auxiliary relays, with a 3 A power supply and battery charger in a NEMA 1/IP30 cabinet. It covers single or dual hazard areas, with cross-zoned or single-zone release chosen from 13 application modes.
NFPA 72 requires one maintenance switch per RAC so the system can be tested without actuating the suppression system, but some jurisdictions may not allow them.
Specifications
| Circuits | Four IDCs, two NACs, two SPMs, two RACs, 3 auxiliary relays |
|---|---|
| AC input | 120 VAC, 60 Hz; 220/230/240 VAC, 50/60 Hz, auto-select |
| Power supply | 3 A at 25.5 VDC during alarm; 3 A maximum available for external loads |
| NACs | Two, Class B, reverse polarity, rated 2 A each |
| RACs | Two, Class B, 2 A maximum per circuit |
| Battery charger | 27.5 VDC; batteries up to 12.7 Ah, suitable for up to 90 hour standby and 10 minutes of alarm |
| Panel current | Standby 100 mA; alarm 264 mA + external loads |
| Operating environment | 32°F to 120°F (0°C to 49°C); up to 93% RH, non-condensing @ 100.4°F (38°C) maximum |
Used with
- 2081-9046 – Coil Supervision Module, one required per RAC
- 4004-9860 – Auxiliary Relay Module, four relays, two maximum
- 4004-9864 – Two Circuit Class A Adapter Module for IDCs, SPMs or NACs
- 2081-9048 – Abort Supervision Module for Dual Hazard SPM
- 2081-9288 – 12.7 Ah 12 V battery, two required
From Simplex datasheet S4004-0002. The datasheet can be downloaded under Documents above.