Product details
| Part number | 4100-9709 |
|---|---|
| Description | ES-Psmstrctrlrnodisplay |
| Category | Fire Alarm Control Panels / 4100ES Panels & Bays |
| System | Simplex 4100ES fire alarm panels |
| Works with | 4100ES (IDNet 2), ES Net or 4120 networks |
| Approvals | UL/ULC |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4100-9709
4100ES Master Controller without a 2x40 display or user interface. Otherwise it matches the 4100-9701: CPU card, an IDNet 2 card for up to 250 addressable/analog points, the ES Power Supply with 110 Ah battery charger, and an external RUI+ communications interface.
The listed currents do not include IDNet, NAC or IDNAC loads; add these separately.
Specifications
| User interface | No 2x40 Display or user interface |
|---|---|
| Addressable capacity (included IDNet 2 card) | Up to 250 addressable/analog points |
| Power supply input | 120 V to 240 V 50/60 Hz |
| Battery charger | 110 Ah |
| Current (supv. / alarm) | 277 mA / 321 mA |
| Operating temperature | 32°F to 120°F (0°C to 49°C) |
Used with
- 4100-5450 – Conventional NAC module
- 4100-5451 – IDNAC addressable notification SLC module
- 4100-2300 – Expansion bay assembly
From Simplex datasheet S4100-1031. The datasheet can be downloaded under Documents above.