Product details
| Part number | 4010-9505 |
|---|---|
| Description | 1 Bay, 2x40, 1 ESMX, 220/240V, Red |
| Category | Fire Alarm Control Panels / 4010ES Panels |
| System | Simplex 4010ES fire alarm panels |
| Works with | MX Loop addressable devices (ESMX Loop channel), Simplex ES Net network (optional NIC), Simplex 4120 network (optional NIC), … |
| Approvals | UL listed (4010ES series: UL 864 Control Units, System) |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4010-9505
The 4010-9505 is a 4010ES addressable fire alarm basic control unit in a red one-bay cabinet, with an English 2x40 LCD operator interface. It has one ESMX Loop channel, Class A or B, for up to 250 addressable MX Loop points, and runs on 220 VAC to 240 VAC. The unit includes an 8 A power supply, four 3 A NACs and three 4 in. x 5 in. option blocks for added modules.
The one-bay cabinet holds batteries up to 33 Ah and is limited to three option block spaces in total.
Specifications
| Operator interface | 2x40 LCD Operator Interface |
|---|---|
| Addressable channel | (1) ESMX Loop Channel, Class A or B, up to 250 addressable MX Loop points |
| Language and voltage | English 220 VAC to 240 VAC |
| Supervisory / alarm current | 364 mA / 432 mA |
| Option blocks | Three 4 in. x 5 in. block |
| Power supply | 8 A power supply with up to 2 A of auxiliary power |
| NACs | 4 onboard Class A or B, 3 A NACs |
| Battery capacity (one-bay cabinet) | 33 Ah max in one bay control cabinet |
Used with
- 4010-6312 – ESMX optional loop mezzanine card
- 4010-9911 – Alarm relay module, mounts on Main System Supply (one max)
- 4010-9910 – City Connect module, mounts on Main System Supply (one max)
- 4606-9102 – 4010ES RUI LCD annunciator, English
- 4100-5128 – Battery distribution terminal block, needed when battery wiring leaves the box
From Simplex datasheet S4010-0006. The datasheet and UL listing can be downloaded under Documents above.