Product details
| Part number | 4081-9004 |
|---|---|
| Description | EOL, 6.8K 1/2W |
| Category | Enclosures, Doors & Accessories / EOL, Surge, Barriers & Small Parts |
| System | Simplex fire alarm systems |
| Works with | 4090-9001 and 4090-9051 supervised IAMs (IDNet, MAPNET II) |
| Approvals | UL listed to Standard 864 |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4081-9004
End-of-line resistor harness, 6.8 kΩ, 1/2 W, ±5%, for Class B circuits where an end-of-line resistor is needed at a remote location to monitor wiring continuity. It is the standard end-of-line resistor for supervising normally open contacts on Simplex 4090-9001 and 4090-9051 supervised IAMs. The resistor leads are crimped to 18 AWG wires and covered with heat shrink tubing.
This harness is UL listed only; it is not ULC, FM, MEA (NYC) or CSFM approved.
Specifications
| Resistance | 6.8 kΩ, 1/2 W, ± 5% |
|---|---|
| Reference number | 733-886 |
| Overall length | Approximately 9-1/2" (241 mm) |
| Wire length | 7" (178 mm) ± 1" (25 mm) |
| Wire | 18 AWG (0.82 mm²); insulation 600 V, black |
| Leads | Stripped 0.5" (13 mm); tinned |
Used with
- 4090-9051 – Supervised IAM, encapsulated with wire leads
- 4090-9001 – Supervised IAM with screw terminals
From Simplex datasheet S4081-0003. The datasheet can be downloaded under Documents above.