Product details
| Part number | 2081-9027 |
|---|---|
| Description | Transient Cube |
| Category | Enclosures, Doors & Accessories / EOL, Surge, Barriers & Small Parts |
| System | Simplex fire alarm systems |
| Works with | 4100ES, 4100U, 4100, 4120, 4007ES, 4010ES, 4020, IDNet and MAPNET II monitor circuits |
| Approvals | UL 497B listed as an Isolated Loop Circuit Protector; ULC-S527 listed as a surge suppressor; CSFM listed |
| Availability | On request, ask for lead time |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 2081-9027
Transient protector for fire alarm circuits that leave or enter a building, such as DC power up to 200 mA, monitor circuits, audio risers and firefighter telephone risers. It gives line-to-line and line-to-earth protection in a small beige epoxy package. Install it as close as possible to the point where the wiring leaves or enters the building, in a dedicated metal box.
Wiring protected by ILCPs must stay on one contiguous property and must not exceed 3270 ft (1 km).
Specifications
| Continuous current | 200 mA maximum |
|---|---|
| Line-to-line voltage | Continuous: 38 VDC, 28 VAC RMS; Clamping: 47 V typical |
| Line-to-earth voltage | Continuous: 45 VDC, 35 VAC RMS; Clamping: 56 V typical |
| Series resistance | 3 Ω/line |
| Dimensions | 2 7/16” W x 1 ⅜” D x 1 1/16” H (62 mm x 35 mm x 27 mm) |
| Electrical box | 4” (102 mm) square box, 2 ⅛” (54 mm) minimum depth |
| Temperature / humidity | 32° F to 120° F (0° C to 49° C); 10-95% RH, at 30° C |
| Leads | Color coded 18 AWG signal leads, 10” long; green 14 AWG ground lead |
Used with
- 2081-9028 – ILCP for higher current, up to 5 A
- 2081-9044 – Overvoltage protector (UL 864, up to 200 mA)
From Simplex datasheet S2081-0007. The datasheet can be downloaded under Documents above.