Product details
| Part number | 4098-5289 |
|---|---|
| Description | MX SSD Heat Sensor + Isolator |
| Category | Detectors & Bases / Smoke, Heat & Multi Sensors |
| System | Simplex TrueAlarm detectors and TrueAlert appliances |
| Works with | 4100ES (MX Loop Module), 4010ES (MX Loop Module), 4007ES (MX Loop Module) |
| Approvals | UL listed to UL 521 |
| Availability | In stock in Riyadh |
| Support | Selection, compatibility and programming help from our engineers |
Need it for a project?
Tell us the quantity and the panel or system it is for. We confirm compatibility, price and delivery, and can install and program it.
About the 4098-5289
Addressable heat sensor for Simplex panels with an MX Loop Module; it sends analog temperature readings to the control unit. Alarm settings of 135 °F (57 °C) or 200 °F (93 °C), with or without rate-of-rise, are selected at the control unit. It has a built-in isolator and is addressed with the DIP switch or the Digital Enrollment app.
Rated for indoor use only (sensors are IP44).
Specifications
| Heat detection settings | 135 °F (57 °C) or 200 °F (93 °C), with or without rate-of-rise |
|---|---|
| Rate-of-rise | 15 °F (8.4 °C) per minute |
| Max. ceiling ambient, 135 °F setting | 100 °F (38 °C) |
| Max. ceiling ambient, 200 °F setting | 150 °F (65.6 °C) |
| Supervisory current | 350 µA |
| Alarm current | 4.0 mA maximum in alarm |
| Dimensions | 108 mm x 42 mm (4.252 in. x 1.653 in.) |
| Communications | MX Loop, one address for each sensor base |
Used with
- 4098-5260 – 4 in. Continuity Base 4B-C
- 4098-5217 – Addressable loop powered sounder base
- 4098-5220 – Addressable loop powered sounder-beacon base
- 2098-9808 – Remote LED alarm indicator
- 4098-5276 – Address flags (pack of 100)
From Simplex datasheet S4906-0020. The datasheet and UL listing can be downloaded under Documents above.